MHSA10B
MHSA10B
Vox Shield Extended Warranty Program

Product warranties and services are handled through our industrial partner, VoxShield. Our partnership with VoxShield allows for seamless, timely turnaround times without you, our valued customer, having to make any additional phone calls or work with anyone but your CPUBoards.com representative. VoxShield offers a completely customizable warranty and service program to fit any budget, timeline, or project. For more information, ask your sales representative or click here.
Repairs
CPUBoards.com is equipped to repair or replace industrial electronic equipment spanning all areas of the industry. While we diagnose and prepare your product for repair, we will simultaneously attempt to locate a replacement, finding the quickest, most efficient solution to getting you back up and running in the least amount of time possible. If you need something repaired, contact us or click here to learn more.
Return Policy
This item is covered by CPUBoards.com's Standard Return Policy.
- Return for a refund within: 30 Days*
- Return for replacement within: 30 Days
- *Restocking Fee Applies
Quick Specs
| Casing (Enclosure) | Fully Enclosed |
| Input Type | DC |
| Output Type | DC |
| view all specs | |
Full Product Specifications
Download Datasheet| Input Circuit | Protection 35 amp fuse is located in the positive input lead of each converter module. |
| Input Current | 210 amps maximum (at full load with eight 10 amp modules, 21VDC input) |
| Input Efficiency | 87% typical |
| Input Filtering | Noise reflected back to the battery is less than 32dBrnC and is within the parameters set forth in Telcordia technical reference TR-TSY-000009, using test measurements in PUB43802, pages 5 and 6. |
| Input Voltage | 24.0 volts DC nominal, with range of 21 to 28 volts DC |
| Output Current | 10 amps per DC-DC converter module, up to a total of 80 amps per shelf with eight modules installed. |
| Output Dynamic Response | For a step load change of 50% within the range of 10% to 100% of full rated current, the maximum voltage transient will not exceed 5% of the initial steady state voltage. |
| Output Filtering | Voice band noise is less than 32dBrnC. Wide band noise does not exceed 250 mV peak to peak over the frequency range of 0 to 20 MHz. Wide band noise does not exceed 30 mV rms over the frequency range of 0 Hz to 20 MHz. |
| Output Regulation | Steady state output voltage remains within ±1 volt of the pre-adjusted voltage for any load current from no load to full load and over the specified input voltage range. |
| Output Voltage | -48.0 VDC |